LCD Display Overview
Information Screens
Settings Configuration
Advanced Information
Advanced Settings
Modbus Tables
Changelog
G100
HV Meter
Advanced Information
Navigation
1
Press ENTER to open main menu
2
Scroll to 'Advanced Info' using UP/DOWN
3
Press ENTER to access advanced screens
4
Use UP/DOWN to navigate between screens
Screen 1: Event Logs
E1:OV-G Current
T:15/03/24
14:30
Format:
E#: Event number and description
Time:
T:DD/MM/YY HH:MM format
Events:
Includes: Normal operation, Comm failures, Over-generation, Fault resets
Nav:
UP/DOWN to view history, Hold ESC 5s to clear
Screen 2: Inverter Power
i1:1500W
i2:1200W
i3:OFFLINE
i4:SLEEPING
Format:
i#:XXXW where XXX is power in watts
OFFLINE:
Shown as 0xFFFFFFFE - No communication
SLEEPING:
Shown as 0xFFFFFFFF - Sleep mode
Nav:
UP/DOWN to view more inverters
Screen 3: Energy Records
PV:1234kWh
Load:890kWh
Imp:456kWh
Exp:123kWh
PV:
Total solar generation (kWh)
Load:
Total consumption (kWh)
Imp:
Total grid import (kWh)
Exp:
Total grid export (kWh)
Screen 4: Communications
i1:50ms
i2:45ms
i3:60ms
i4:55ms
Format:
i#:XXXms shows response time
Range:
Typical range 30-100ms
Warning:
Higher values indicate poor connection
Nav:
UP/DOWN to view more inverters
Screen 5: Inverter Idle Times
i1:30s
i2:5m
i3:2hr
i4:1d
Format:
Time since last communication
Units:
s=seconds, m=minutes, hr=hours, d=days
Auto:
Units change based on duration
Nav:
UP/DOWN to view more inverters
Screen 6: Packet Loss
Inv Pkt L:
0.50%
Meter Pkt L:
0.10%
Inv:
Inverter communication reliability
Meter:
Meter communication reliability
Calc:
Percentage of failed requests
Good:
Values under 1% indicate good connection